The RM10TE00 is a white phase loss/sequence relay designed for monitoring the phase sequence and detecting phase loss in three-phase electrical systems. It is typically used in industrial and commercial applications to ensure the proper functioning of electrical equipment. Phase Loss Detection: The RM10TE00 relay detects when one or more phases in a three-phase system are lost or disconnected. It provides a warning or alarm signal to alert users of the issue, helping to prevent damage to motors, machinery, and other connected equipment. Phase Sequence Monitoring: In addition to phase loss detection, the relay also monitors the correct sequence of phases in a three-phase system. It ensures that the phases are in the correct order (L1, L2, L3) to prevent improper operation or damage to equipment. Adjustable Parameters: The RM10TE00 relay allows for adjustable parameters such as voltage thresholds and time delays, enabling customization to suit specific application requirements and system configurations. LED Indicators: The relay is equipped with LED indicators that provide visual indication of the status of each phase and the sequence of phases. This allows for easy monitoring and troubleshooting. Easy Installation: The RM10TE00 relay is designed for easy installation and integration into electrical systems. It typically features a compact form factor and is DIN rail mounted, allowing for convenient and space-saving installation. Schneider Electric Support: Schneider Electric provides comprehensive support for its products, including technical documentation, user guides, and customer service. For specific information and guidance related to the RM10TE00 relay, it is recommended to refer to the product datasheet or contact Schneider Electric directly.

SKU: RM10TE00
  • Product Info

    Range of product Harmony Relay
    Relay type Multifunction control relay
    Product or component type Modular measurement and control relays
    Product specific application For 3-phase supply
    Relay name RM10TE
    Relay monitored parameters Phase sequence
    Asymmetry
    Undervoltage and overvoltage in window mode
    Phase failure detection
    time delay Adjustable 0.1...10 s, +/- 10 % of the full scale value
    Switching capacity in VA 1250 VA
    Measurement range 183...528 V AC
    Complementary
    Reset time 1500 ms time delay
    Maximum switching voltage 250 V AC
    250 V DC
    Minimum switching current 10 mA at 5 V DC
    Maximum switching current 5 A AC
    5 A DC
    Supply voltage limits 183…528 V AC
    Control circuit voltage limits - 12 % + 10 % Un
    Power consumption in VA 0…22 VA at 400 V AC 50 Hz
    control circuit frequency 50...60 Hz +/- 10 %
    Output contacts 1 C/O
    Nominal output current 5 A
    Hysteresis 2 %
    delay at power up 650 ms
    Maximum measuring cycle 150 ms measurement cycle as true rms value
    Threshold adjustment voltage 2...20 % of Un selected
    -2...-17 % in the range 220 V AC
    +2...+10 % in the range 480 V AC
    -2...-12 % in the range 208 V AC
    Voltage range 208...480 V phase to phase
    Adjustment of asymmetry threshold 5...15 % of Un selected
    Repeat accuracy 0.5 % for input and measurement circuit
    3 % for time delay
    Measurement error < 0.05 %/°C with temperature variation
    < 1 % over the whole range with voltage variation
    Phase failure sensitivity 0.7 Un
    Response time < 200 ms (in the event of a fault)
    Marking CE
    Overvoltage category III conforming to IEC 60664-1
    Insulation resistance > 500 MOhm at 500 V DC conforming to IEC 60255-5
    > 500 MOhm at 500 V DC conforming to IEC 60664-1
    [Ui] rated insulation voltage 400 V conforming to IEC 60664-1
    Supply frequency 50/60 Hz +/- 10 %
    Operating position Any position without derating
    Connections - terminals Screw terminals, 1 x 0.5...1 x 4 mm² (AWG 20...AWG 11) solid without cable end
    Screw terminals, 2 x 0.5...2 x 2.5 mm² (AWG 20...AWG 14) solid without cable end
    Screw terminals, 1 x 0.2...1 x 2.5 mm² (AWG 24...AWG 12) flexible with cable end
    Screw terminals, 2 x 0.2...2 x 1.5 mm² (AWG 24...AWG 16) flexible with cable end
    Tightening torque 0.6…1 N.m conforming to IEC 60947-1
    Housing material Self-extinguishing plastic
    Local signalling LED (green) for power ON
    LED (yellow) for relay ON
    Mounting support 35 mm symmetrical DIN rail conforming to IEC 60715
    Electrical durability 100000 cycles
    Mechanical durability 30000000 cycles
    Operating rate <= 360 operations/hour full load
    Utilisation category AC-12 conforming to IEC 60947-5-1
    AC-13 conforming to IEC 60947-5-1
    AC-14 conforming to IEC 60947-5-1
    AC-15 conforming to IEC 60947-5-1
    DC-12 conforming to IEC 60947-5-1
    DC-13 conforming to IEC 60947-5-1
    Safety reliability data B10d = 470000
    MTTFd = 502.2 years
    Width 17.5 mm
    Net weight 0.13 kg
    Environment
    Electromagnetic compatibility Emission standard for industrial environments conforming to IEC 61000-6-4
    Emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3
    Immunity for industrial environments conforming to IEC 61000-6-2
    Standards IEC 60255-1
    product certifications C-Tick
    UL
    GOST
    CSA
    GL
    Directives 89/336/EEC - electromagnetic compatibility
    73/23/EEC - low voltage directive
    Ambient air temperature for storage -40…70 °C
    Ambient air temperature for operation -20…50 °C
    Relative humidity 95 % at 55 °C conforming to IEC 60068-2-30
    Vibration resistance 0.35 mm (f= 5…57.6 Hz) conforming to IEC 60068-2-6
    1 gn (f= 57.6…150 Hz) conforming to IEC 60255-21-1
    Shock resistance 15 gn for 11 ms conforming to IEC 60255-21-1
    IP degree of protection IP20 (terminals) conforming to IEC 60529
    IP30 (casing) conforming to IEC 60529
    Pollution degree 3 conforming to IEC 60664-1
    Dielectric test voltage 2 kV, 1 min AC 50 Hz conforming to IEC 60255-5
    2 kV, 1 min AC 50 Hz conforming to IEC 60664-1
    Non-dissipating shock wave 4 kV conforming to IEC 60255-5
    4 kV conforming to IEC 60664-1
    4 kV conforming to IEC 61000-4-5
    Packing Units
    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 2.7 cm
    Package 1 Width 7.8 cm
    Package 1 Length 9.7 cm
    Package 1 Weight 92 g
    Unit Type of Package 2 S02
    Number of Units in Package 2 48
    Package 2 Height 15 cm
    Package 2 Width 30 cm
    Package 2 Length 40 cm
    Package 2 Weight 4830 g
    Unit Type of Package 3 P06
    Number of Units in Package 3 768
    Package 3 Height 70 cm
    Package 3 Width 60 cm
    Package 3 Length 80 cm
    Package 3 Weight 82280 g
  • Return & Refund Policy

  • Shipping Info

No Reviews YetShare your thoughts. Be the first to leave a review.
bottom of page