TeSys T is a motor management system that provides full motor monitoring, control, and protection when used with short circuit protection and a contactor. TeSys T manages most critical processes while reducing downtime and increasing productivity. TeSys T is a flexible system that integrates seamlessly into your automation system through five major communication protocols. TeSys T predicts what will happen in the process, as it accurately monitors current, voltage, and power over a wide range. This controller is the central component in the motor management system. The module manages the basic functions of the motor management system. It manages the measurement of 3 phase current via integral current transformers from 0.4 to 100 A or up to 810 A by external current transformers. It also measures ground current with internal or external ground sensors, motor temperature and the inputs and outputs for the various motor control modes, detected fault management and other functions. DeviceNet protocol is used by this controller. This module has 6 discrete logic inputs, 3 relay logic outputs and a relay output for detected fault signaling overload relay. The current range of this controller is 0.4 to 8 amperes. 120 to 240 VAC is used to power this controller. Controller has the following certifications: UL, CSA NOM, ATEX, BV, EAC, RINA, LROS, DNV, ABS, GL, KERI, RMRoS, C-Tick and CCC.

SKU: LTMR08DFM
  • Product Info

    Range TeSys
    Product name TeSys T
    Device short name LTMR
    Product or component type Motor controller
    Device application Equipment monitoring and control
    Measurement current 0.4…8 A
    [Us] rated supply voltage 100...240 V AC 50/60 Hz
    Current consumption 8...62.8 mA
    Supply voltage limits 93.5…264 V AC
    communication port protocol DeviceNet
    Bus type DeviceNet ISO 1198 interface, addressing 1...64, transmission rate 125...500 kbit/s, terminal block with 4 twisted shielded pairs cable
    Environment
    Standards UL 508
    IACS E10
    CSA C22.2 No 14
    IEC 60947-4-1
    EN 60947-4-1
    product certifications KERI
    LROS (Lloyds register of shipping)
    CSA
    ATEX
    UL
    DNV
    C-Tick
    RMRoS
    CCC
    RINA
    ABS
    EAC
    GL
    NOM
    BV
    Protective treatment 12 x 24 hour cycles conforming to EN/IEC 60068-2-30
    48 h conforming to EN/IEC 60070-2-11
    TH conforming to EN/IEC 60068
    Fire resistance 650 °C conforming to EN/IEC 60695-2-12
    960 °C conforming to UL 94
    Ambient air temperature for operation -20…60 °C
    Ambient air temperature for storage -40…80 °C
    Operating altitude <= 2000 m without derating
    Mechanical robustness Vibrations mounted on symmetrical rail: 1 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
    Vibrations plate mounted: 4 Gn, 5...300 Hz conforming to EN/IEC 60068-2-6
    Shocks half sine wave acceleration: 15 Gn for 11 ms conforming to EN/IEC 60068-2-27
    IP degree of protection IP20
    Packing Units
    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 7.0 cm
    Package 1 Width 10.0 cm
    Package 1 Length 13.5 cm
    Package 1 Weight 520.0 g
    Unit Type of Package 2 S02
    Number of Units in Package 2 10
    Package 2 Height 15.0 cm
    Package 2 Width 30.0 cm
    Package 2 Length 40.0 cm
    Package 2 Weight 5.555 kg