CVS100B ETS 2.2 100A 3P circuit breaker front

CVS100B ETS 2.2 100A 3P circuit breaker

This device is a 3 poles 3d fixed circuit breaker with a high level of performance and cost-saving functionality. It is an optimal choice for small and medium-sized buildings protection applications. The breaking capacity (Icu) is 25kA rms at 415VAC 50/60Hz. The operational voltage is 440VAC 50/60Hz. This product embeds a ETS 2.2 electric trip unit. This 3 poles version (105mm x 161mm x 86mm) comes with a variety of optional functions and accessories. EasyPact CVS100B is compliant with international standards (IEC 60947, EN 60947, CCC, CB).

SKU: LV510551
  • Product Info

    Range EasyPact
    Product name EasyPact CVS
    Device short name CVS100B
    Product or component type Circuit breaker
    Device application Distribution
    Poles description 3P
    Protected poles description 3D
    Earth leakage protection (Vigi add on) Without
    [In] rated current 100 A at 40 °C
    Network type AC
    utilisation category Category A
    [Icu] Breaking capacity  40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    25 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
    Trip unit name ETS 2.2
    Trip unit technology Electronic
    Protection type Short time short-circuit protection with fixed delay
    Overload protection (long time)
    Instantaneous short-circuit protection
    Complementary
    [Uimp] rated impulse withstand voltage 8 kV conforming to EN/IEC 60947-2
    Network frequency 50/60 Hz
    Breaking capacity code B
    [Ics] rated service breaking capacity 15 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
    25 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
    40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
    Mechanical durability 30000 cycles
    Electrical durability 12000 cycles 415 V In conforming to IEC 60947-2
    Control type Toggle
    Long time pick-up adjustment type Ir Adjustable 9 settings
    long time pick-up adjustment range 40...100 A
    Long time delay adjustment type Fixed
    [tr] long-time delay adjustment range 11 s at 7.2 x Ir
    16 s at 6 x Ir
    400 s at 1.5 x Ir
    Short-time pick-up adjustment type Isd Adjustable 9 settings
    [Isd] short-time pick-up adjustment range 1.5...10 x Ir
    Short-time delay adjustment type Fixed
    [tsd] short-time delay adjustment range 0.02 s
    Instantaneous pick-up adjustment type Ii Fixed
    instantaneous pick-up adjustment range 1500 A
    Contact position indicator Yes
    Mounting mode Fixed
    mounting support Backplate
    Upside connection Front
    downside connection Front
    Connections - terminals Screw connection
    Connection pitch 35 mm
    Compatibility code CVS100
    Width 105 mm
    Depth 86 mm
    height 161 mm
    Net weight 2.04 kg
    Environment
    Standards EN 60947-2
    IEC 60947-2
    product certifications CCC
    CB
    Electrical shock protection class Class II
    Pollution degree 3 conforming to IEC 60664-1
    IP degree of protection IP40
    Ambient air temperature for operation -25…70 °C
    Ambient air temperature for storage -50…85 °C
    Packing Units
    Unit Type of Package 1 PCE
    Number of Units in Package 1 1
    Package 1 Height 11.300 cm
    Package 1 Width 13.500 cm
    Package 1 Length 19.000 cm
    Package 1 Weight 1.715 kg
    Unit Type of Package 2 S02
    Number of Units in Package 2 4
    Package 2 Height 15.000 cm
    Package 2 Width 30.000 cm
    Package 2 Length 40.000 cm
    Package 2 Weight 7.120 kg
    Unit Type of Package 3 P12
    Number of Units in Package 3 64
    Package 3 Height 45.000 cm
    Package 3 Width 80.000 cm
    Package 3 Length 120.000 cm
    Package 3 Weight 125.920 kg