Complementary |
Device application |
Power factor control
Load control
Power monitoring |
Type of measurement |
Current
Voltage
Frequency
Power factor
RPM |
Metering type |
Unbalance current
Power factor and displacement PF (signed, four quadrant)
Rotation speed
Voltage U21, U32, U13, V1, V2, V3
Frequency
Average voltage Vavg
Percentage of load
Unbalance voltage
Calculated neutral current
Phase currents
Average current Iavg |
counter functions |
Power outage counting
ON hour counting
Power interruption |
[Us] rated supply voltage |
44...277 V AC 45...65 Hz
44...277 V DC |
Network frequency |
60 Hz
50 Hz |
[In] rated current |
1 A
5 A |
type of network |
3P
2P
2P + N
1P + N
3P + N |
Maximum power consumption in VA |
4 VA at 240 V between phase and neutral |
Maximum power consumption in W |
2 W at 240 V |
display type |
7 segments LED |
Display colour |
Red |
Messages display capacity |
3 fields of 4 characters |
Display digits |
12 digit(s) - 14.2 mm in height |
communication of data |
Revolution speed
All counters
Percentage of load
Reading of measurements |
Tamperproof of settings |
Protected by access code |
Sampling rate |
32 samples/cycle |
Measurement current |
5…6000 mA |
Signal |
Voltage (impedance 5 MOhm)4 x
Current 0.005...10 A (impedance 0.3 MOhm)6 x |
Measurement voltage |
46…277 V AC 50...60 Hz between phase and neutral
80…480 V AC 50...60 Hz between phases
277…999000 V AC 50...60 Hz with external VT |
Frequency measurement range |
45…65 Hz |
Measurement accuracy |
Frequency +/- 0.05 %
Power factor +/- 0.01
Current +/- 1 %
Voltage +/- 1 % |
Number of outputs |
0 |
Demand intervals |
1 s |
Local signalling |
Green LED: activity
Red LED: output signal 1...9999000 pulse/ k_h (kWh, kVAh, kVARh) |
Communication port protocol |
Modbus at 4800 bps, 9600 bps, 19200 bps, 38.4 Kbps even/odd or none - 2 wires, insulation 2500 V |
Communication port support |
Screw terminal block: RS485 |
Material |
Polycarbonate |
Flame retardance |
V-0 conforming to UL 94 |
Mounting mode |
Flush-mounted |
Mounting support |
Framework |
Fixing mode |
By clamp |
provided equipment |
Installation guide |
installation category |
III |
Type of installation |
Indoor installation |
Measurement category |
Category III 35…480 V |
Electrical insulation class |
Class II |
Connections - terminals |
Current circuit: screw clamp terminals (bottom) 2.08…3.31 mm² cable(s)
Voltage circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s)
Control circuit: screw clamp terminals (top) 0.82…3.31 mm² cable(s) |
Tightening torque |
Current circuit: 0.9…1 N.m Philips No 2 screwdriver
Voltage circuit: 0.9…1 N.m Philips No 2 screwdriver
Control circuit: 0.9…1 N.m Philips No 2 screwdriver
Communication: 0.5…0.6 N.m Philips No 2 screwdriver |
Wire stripping length |
Current circuit: 3.68 mm
Voltage circuit: 7 mm
Control circuit: 7 mm
Communication: 7 mm |
Standards |
IEC 61010-1:ed. 3
UL 61010-1:ed. 3 |
Product certifications |
CE conforming to IEC 61010-1
CULus conforming to UL 61010-1
CULus conforming to CSA C22.2 No 61010-1
C-Tick |
Width |
96 mm |
Depth |
13 mm outside:
49 mm panel: |
height |
96 mm |
Net weight |
300 g |