Complementary |
height |
42 mm |
Width |
30 mm |
Depth |
52 mm |
Terminals description ISO n°1 |
(21-22)NC |
Net weight |
0.037 kg |
Device mounting |
Fixing hole - diameter: 22.5 mm 22.3 +0.4/0 conforming to IEC 60957-5-1 |
Fixing mode |
Fixing nut recommended torque: 2.2 N.m (+/- 0.2 N.m) |
Contacts usage |
Standard contacts |
Positive opening |
With conforming to IEC 60947-5-1 appendix K |
Operating travel |
1.5 mm (NC changing electrical state)
2.6 mm (NO changing electrical state)
4.3 mm (total travel) |
Operating force |
3.5 N NC changing electrical state
3.8 N NO changing electrical state |
Mechanical durability |
5000000 cycles |
Tightening torque |
0.8…1.2 N.m conforming to IEC 60947-1 |
Shape of screw head |
Cross compatible with Philips no 1 screwdriver
Cross compatible with pozidriv No 1 screwdriver
Slotted compatible with flat Ø 4 mm screwdriver
Slotted compatible with flat Ø 5.5 mm screwdriver |
Contacts material |
Silver alloy (Ag/Ni) |
Short-circuit protection |
10 A cartridge fuse type gG conforming to IEC 60947-5-1 |
[Ith] conventional free air thermal current |
10 A conforming to IEC 60947-5-1 |
[Ui] rated insulation voltage |
600 V (pollution degree 3) conforming to IEC 60947-1 |
[Uimp] rated impulse withstand voltage |
6 kV conforming to IEC 60947-1 |
[Ie] rated operational current |
3 A at 240 V, AC-15, A600 conforming to IEC 60947-5-1
0.55 A at 125 V, DC-13, Q600 conforming to IEC 60947-5-1
0.1 A at 600 V, DC-13, Q600 conforming to IEC 60947-5-1
0.27 A at 250 V, DC-13, Q600 conforming to IEC 60947-5-1
1.2 A at 600 V, AC-15, A600 conforming to IEC 60947-5-1
6 A at 120 V, AC-15, A600 conforming to IEC 60947-5-1 |
Electrical durability |
1000000 cycles AC-15, 2 A at 230 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C
1000000 cycles AC-15, 3 A at 120 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C
1000000 cycles AC-15, 4 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C
1000000 cycles DC-13, 0.2 A at 110 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C
1000000 cycles AC-13, 0.5 A at 24 V, operating rate <3600 cyc/h, load factor: 0.5 conforming to IEC 60947-5-1: appendix C |
Electrical reliability |
Λ < 10exp(-6) at 5 V and 1 mA in clean environment conforming to IEC 60947-5-4
Λ < 10exp(-8) at 17 V and 5 mA in clean environment conforming to IEC 60947-5-4 |
Device presentation |
Complete product |
customizable |
No |
Customizable |
0 |
Compatibility code |
XB5 |